| CVE-2022-37952 | TRUNG BÌNH6.1 | A reflected cross-site scripting (XSS) vulnerability exists in the iHistorian Data Display of WorkstationST (<v07.09.15) could allow an attacker to compromise a victim's browser. WorkstationST is only deployed in specific, controlled environments rendering attack complexity significantly higher than if the attack were | 25/08/2022 |
| CVE-2021-44477 | CAO7.5 | GE Gas Power ToolBoxST Version v04.07.05C suffers from an XML external entity (XXE) vulnerability using the DTD parameter entities technique that could result in disclosure and retrieval of arbitrary data on the affected node via an out-of-band (OOB) attack. The vulnerability is triggered when input passed to the XML p | 25/03/2022 |
| CVE-2021-27430 | TRUNG BÌNH6.8 | GE UR bootloader binary Version 7.00, 7.01 and 7.02 included unused hardcoded credentials. Additionally, a user with physical access to the UR IED can interrupt the boot sequence by rebooting the UR. | 23/03/2022 |
| CVE-2022-23921 | CAO7.8 | Exploitation of this vulnerability may result in local privilege escalation and code execution. GE maintains exploitation of this vulnerability is only possible if the attacker has login access to a machine actively running CIMPLICITY, the CIMPLICITY server is not already running a project, and the server is licensed f | 25/02/2022 |
| CVE-2019-18243 | TRUNG BÌNH5.5 | HMI/SCADA iFIX (Versions 6.1 and prior) allows a local authenticated user to modify system-wide iFIX configurations through the registry. This may allow privilege escalation. | 18/02/2021 |
| CVE-2019-18255 | TRUNG BÌNH5.5 | HMI/SCADA iFIX (Versions 6.1 and prior) allows a local authenticated user to modify system-wide iFIX configurations through section objects. This may allow privilege escalation. | 18/02/2021 |
| CVE-2020-27267 | NGHIÊM TRỌNG9.1 | KEPServerEX v6.0 to v6.9, ThingWorx Kepware Server v6.8 and v6.9, ThingWorx Industrial Connectivity (all versions), OPC-Aggregator (all versions), Rockwell Automation KEPServer Enterprise, GE Digital Industrial Gateway Server v7.68.804 and v7.66, and Software Toolbox TOP Server all 6.x versions, are vulnerable to a hea | 14/01/2021 |
| CVE-2020-27265 | NGHIÊM TRỌNG9.8 | KEPServerEX: v6.0 to v6.9, ThingWorx Kepware Server: v6.8 and v6.9, ThingWorx Industrial Connectivity: All versions, OPC-Aggregator: All versions, Rockwell Automation KEPServer Enterprise, GE Digital Industrial Gateway Server: v7.68.804 and v7.66, Software Toolbox TOP Server: All 6.x versions are vulnerable to a stack- | 14/01/2021 |
| CVE-2020-27263 | NGHIÊM TRỌNG9.1 | KEPServerEX: v6.0 to v6.9, ThingWorx Kepware Server: v6.8 and v6.9, ThingWorx Industrial Connectivity: All versions, OPC-Aggregator: All versions, Rockwell Automation KEPServer Enterprise, GE Digital Industrial Gateway Server: v7.68.804 and v7.66, Software Toolbox TOP Server: All 6.x versions, are vulnerable to a heap- | 14/01/2021 |
| CVE-2020-16244 | CAO7.2 | GE Digital APM Classic, Versions 4.4 and prior. Salt is not used for hash calculation of passwords, making it possible to decrypt passwords. This design flaw, along with the IDOR vulnerability, puts the entire platform at high risk because an authenticated user can retrieve all user account data and then retrieve the a | 23/09/2020 |
| CVE-2020-16240 | TRUNG BÌNH5.3 | GE Digital APM Classic, Versions 4.4 and prior. An insecure direct object reference (IDOR) vulnerability allows user account data to be downloaded in JavaScript object notation (JSON) format by users who should not have access to such functionality. An attacker can download sensitive data related to user accounts witho | 23/09/2020 |
| CVE-2020-6992 | TRUNG BÌNH6.7 | A local privilege escalation vulnerability has been identified in the GE Digital CIMPLICITY HMI/SCADA product v10.0 and prior. If exploited, this vulnerability could allow an adversary to modify the system, leading to the arbitrary execution of code. This vulnerability is only exploitable if an attacker has access to a | 15/04/2020 |
| CVE-2019-6566 | CAO7.8 | GE Communicator, all versions prior to 4.0.517, allows a non-administrative user to replace the uninstaller with a malicious version, which could allow an attacker to gain administrator privileges to the system. | 09/05/2019 |
| CVE-2019-6564 | CAO7.8 | GE Communicator, all versions prior to 4.0.517, allows a non-administrative user to place malicious files within the installer file directory, which may allow an attacker to gain administrative privileges on a system during installation or upgrade. | 09/05/2019 |
| CVE-2019-6548 | NGHIÊM TRỌNG9.8 | GE Communicator, all versions prior to 4.0.517, contains two backdoor accounts with hardcoded credentials, which may allow control over the database. This service is inaccessible to attackers if Windows default firewall settings are used by the end user. | 09/05/2019 |
| CVE-2019-6546 | CAO7.8 | GE Communicator, all versions prior to 4.0.517, allows an attacker to place malicious files within the working directory of the program, which may allow an attacker to manipulate widgets and UI elements. | 09/05/2019 |
| CVE-2019-6544 | TRUNG BÌNH5.6 | GE Communicator, all versions prior to 4.0.517, has a service running with system privileges that may allow an unprivileged user to perform certain administrative actions, which may allow the execution of scheduled scripts with system administrator privileges. This service is inaccessible to attackers if Windows defaul | 09/05/2019 |
| CVE-2018-15362 | NGHIÊM TRỌNG9.1 | XXE in GE Proficy Cimplicity GDS versions 9.0 R2, 9.5, 10.0 | 07/12/2018 |
| CVE-2018-17925 | TRUNG BÌNH4.8 | Multiple instances of this vulnerability (Unsafe ActiveX Control Marked Safe For Scripting) have been identified in the third-party ActiveX object provided to GE iFIX versions 2.0 - 5.8 by Gigasoft. Only the independent use of the Gigasoft charting package outside the iFIX product may expose users to the reported vulne | 10/10/2018 |
| CVE-2017-7908 | CAO7.6 | A heap-based buffer overflow exists in the third-party product Gigasoft, v5 and prior, included in GE Communicator 3.15 and prior. A malicious HTML file that loads the ActiveX controls can trigger the vulnerability via unchecked function calls. | 02/10/2018 |